3512B (50 Hz) Generator Set

Producing reliable power from 1360 to 1600 kVA at 50 Hz, our 3512B diesel generator sets are made to meet your mission critical, continuous, standby and prime applications. We've designed each to ISO 8528-5 transient response requirements and to accept 100% rated load in one step. Generator sets offer both low fuel consumption and low emission systems.

Generator SpecSizer
Specifications
Equipment
Product Brochures
Attachments
Units: US Metric
Generator Set Specifications
Standby Rating
1600/1500 kVA
Prime Power Rating
1500/1360 kVA
Emissions/Fuel Strategy
Low Fuel, Low Emissions
Voltage
380 to 415 Volts
Frequency
50 Hz
Speed
1500 rpm
Duty Cycle
Standby, Mission Critical, Prime
Maximum Rating
1600 kVA
Minimum Rating
1360 kVA
Engine Specifications
Engine Model
3512B TA, V-12, 4-Stroke Water-Cooled Diesel
Bore
6.69 in
170 mm
Stroke
7.48 in
190 mm
Displacement
3161.03 in³
51.8 l
Compression Ratio
14.0:1
Aspiration
TA
Fuel System
Electronic Unit Injection
Governor Type
ADEMâ„¢ A3
Generator Set Dimensions
Length - Minimum
206.6 in
5249 mm
Length - Maximum
215.3 in
5469 mm
Width - Minimum
77.8 in
1975 mm
Width - Maximum
90 in
2286 mm
Height - Maximum
93.2 in
2367 mm
Dry Weight - Genset (minimum)
25010 lb
11350 kg
Dry Weight - Genset (maximum)
26840 lb
12180 kg
Standard Equipment
Air Inlet System
Air Inlet
Cooling
Control Panel
Exhaust
Fuel
Control System
Generator
Power Termination
Generator System
Literature
Cooling System
Exhaust System
Fuel System
Generators and Attachments
Governing System
Lube System
Mounting System
Starting / Charging System
General

Switchgear and Paralleling Controls